Výrobní program O firmě Certifikáty Ceník Kontakty
1. Pre-insulated Pipeline Systems
Introduction – General Information
Applied Materials
Medium-Conducting Pipeline
Insulating Layers
Outer Protective Layers
Pipeline and Fittings
PIP 130 A, B, C
PIP 180 A, B, C
PIP 210, 240, 270
PIP 300 A, B, C
Elbows, Branches, Reducers, Compensators, Fixed Points
Accessory Parts - Entries, Pipeline Ends, Expansion Cushions
Mounting Instructions for Pipeline Connection, Coupling Design
Safety Regulations
Handling, Storage
Planning Activity Documents
Earth Works
Thermal Losses of Distribution Systems – k-Coefficient
Heat Dilatation PIP
Solution of Heat Dilatation
Compensating Bodies L, Z, U
Heat Tensioning of Pipeline
Steam Distribution System
Installation Length, Friction Forces, Pipe Cross-Sections
Monitoring System
2. Production Assortment of the Company IZO

Compensation with the Use of Axial Compesators

a) For compensation of dilatation movements there can be used "conventional" axial compensators, too. In case of this solution it is necessary to respect the fact that the pre-insulated pipeline forms a compact unit and from this viewpoint exceeding of shearing stress in the insulating layer can occur at a big dilatation step. On this account, in the routing the sliding foils between the steel pipe and insulation are used, these foils are placed in line according to design and temperature conditions in points of greatest pipeline movement.

b) The more often used axial compensators are so-called lightener (axial compensators with a short stroke). In the routing they are used for sections, where they reach the full stroke (closing) at Tp. Herewith they catch the dilatation, which would have to be compensated by expansion cushions or by pre-tensioning, and assure, that the temperatures above TP and their fluctuation show as a tension in the pipe and not as a movement. The lighteners are set in particular sections according to calculation!

Location of axial compensators with a short stroke (lighteners) in pipeline routing
Lamax – is effected by installation and temperature conditions

« Solution of Heat Dilatation - Heat Tensioning of Pipeline